FERMAX
Referencia: 4921
217,80 € (impuestos inc.)
range | Acti 9 | |
---|---|---|
product name | Acti 9 iC60 RCBO | |
product or component type | Residual current breaker with overcurrent protection (RCBO) | |
device short name | IC60 RCBO | |
device application | Distribution | |
poles description | 4P | |
number of protected poles | 4 | |
[In] rated current | 32 A | |
network type | AC | |
trip unit technology | Thermal-magnetic | |
curve code | C | |
earth-leakage sensitivity | 300 mA | |
earth-leakage protection time delay | Instantaneous | |
earth-leakage protection class | Type AC | |
breaking capacity | Icn 6000 A at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1 Icu 6 kA at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2 | |
suitability for isolation | No conforming to IEC 60947-1 | |
quality labels | IMQ NF VDE KEMA-KEUR |
device location in system | Outgoer | |
---|---|---|
network frequency | 50 Hz | |
[Ue] rated operational voltage | 380...415 V AC 50 Hz | |
magnetic tripping limit | 5...10 x In | |
residual current tripping technology | Voltage independent | |
[Ics] rated service breaking capacity | 6000 A 100 % x Icn at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1 6 kA 100 % x Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2 | |
rated breaking and making capacity | Idm 6000 A at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1 | |
limitation class | 1 conforming to EN/IEC 61009-2-1 | |
[Ui] rated insulation voltage | 500 V AC 50 Hz | |
[Uimp] rated impulse withstand voltage | 4 kV | |
contact position indicator | No | |
control type | Toggle | |
local signalling | ON, OFF, fault trip | |
mounting mode | Clip-on | |
mounting support | DIN rail | |
9 mm pitches | 8 | |
height | 86 mm | |
width | 72 mm | |
depth | 78 mm | |
product weight | 423 g | |
colour | White | |
mechanical durability | 20000 cycles | |
electrical durability | 10000 cycles | |
connections - terminals | Tunnel type terminal, top or bottom rigid wire(s) 1...35 mm² max Tunnel type terminal, top or bottom flexible wire(s) 1...25 mm² max Tunnel type terminal, top or bottom flexible with ferrule wire(s) 1...25 mm² max | |
wire stripping length | 12 mm (top or bottom) | |
tightening torque | 2 N.m | |
earth-leakage protection | Integrated |